PHASE FAILURE, UNDER & OVER VOLTAGE PLUS TIME DELAY - LXPRC 3W to 4W
*
*
S$138.20
  • Under and Over voltage monitoring (Window)
  • Monitors own three phase, 3 or 4 -wire supply
  • Detects phase, loss or neutral loss
  • Adjustable Trip levels and Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product monitors it’s own three-phase supply and for the output relay to energise, all phases must be present and the phase to phase voltages within the set Under/Over trip levels. If any of these conditions are not met, the relay will de-energise. This product operates irrespective of phase sequence.

  • Under and Over voltage monitoring (Window)
  • Monitors own three phase, 3 or 4 -wire supply
  • Detects phase, loss or neutral loss
  • Adjustable Trip levels and Time delay
  • SPDT Relay output
  • 17.5mm wide, DIN Rail mount
  • UL Listed

The product monitors it’s own three-phase supply and for the output relay to energise, all phases must be present and the phase to phase voltages within the set Under/Over trip levels. If any of these conditions are not met, the relay will de-energise. This product operates irrespective of phase sequence.

  • Monitoring function: Under/Over voltage
  • 3-W Monitored supply voltage*: 110V, 208V, 380V, 400V or 415VAC
  • 4-W Monitored supply voltage*: 120V, 127V, 220V, 230V or 240VAC
  • Trip level: Under: 75 – 95%/Over: 105 – 125%
  • Hysteresis: ≈2%
  • Time delay: 0.2 – 10s
  • Output: SPDT 8A @ 250V (AC1)
  • Dimensions(mm): W:17.5 x H:89 x D:66.5

* To be specified when ordering